کليد حرارتی مغناطیسی اشنایدر الکتریک 37 تا 50 آمپر

Motor circuit breaker, TeSys GV3, 3P, 37-50 A, thermal magnetic, EverLink terminals

توضیحات

کلید حرارتی مغناطیسی ۳۷ تا ۵۰ آمپر

کلید حرارتی مغناطیسی اشنایدر الکتریک 37 تا ۵۰ آمپر

 

Motor circuit breaker, TeSys GV3, 3P, 37-50 A, thermal magnetic, EverLink terminals

Main
range
TeSys
product name
TeSys GV3
device short name
GV3P
device application
Motor
trip unit technology
Thermal-magnetic

Complementary

poles description
3P
network type
AC
utilisation category
AC-3 conforming to IEC 60947-4-1
Category A conforming to IEC 60947-2
network frequency
۵۰/۶۰ Hz conforming to IEC 60947-4-1
fixing mode
۳۵ mm symmetrical DIN rail: clipped
Panel: screwed (with 3 x M4 screws)
operating position
Any position
motor power kW
۲۲ kW at 400/415 V AC 50/60 Hz
30 kW at 500 V AC 50/60 Hz
45 kW at 690 V AC 50/60 Hz
breaking capacity
۱۰۰ kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity
۱۰۰ % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
control type
Rotary knob
[In] rated current
۵۰ A
thermal protection adjustment range
۳۷…۵۰ A
magnetic tripping current
۷۰۰ A
[Ue] rated operational voltage
۶۹۰ V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage
۶۹۰ V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current
۵۰ A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage
IEC 60947-2 6 kV
power dissipation per pole
۸ W
mechanical durability
۵۰۰۰۰ cycles
electrical durability
۵۰۰۰۰ cycles for AC-3 at 440 V In
maximum operating rate
۲۵ cyc/h
rated duty
Continuous conforming to IEC 60947-4-1
connections – terminals
EverLink BTR screw connectors 2 cable(s) 1…۲۵ mm² solid
EverLink BTR screw connectors 2 cable(s) 1…۲۵ mm² flexible without cable end
EverLink BTR screw connectors 2 cable(s) 1…۲۵ mm² flexible with cable end
tightening torque
۵ N.m on EverLink BTR screw connectors for cable 25 mm²
8 N.m on EverLink BTR screw connectors for cable 35 mm²
suitability for isolation
Yes conforming to IEC 60947-1
phase failure sensitivity
Yes conforming to IEC 60947-4-1
height
۱۳۲ mm
width
۵۵ mm
depth
۱۳۶ mm
net weight
۰.۹۶ kg