توضیحات

circuit breaker Masterpact NW10H2 – 1000 A – 3 poles – fixed – w/o trip unit

 

۴۸۰۱۶

 

کلید هوایی ۱۰۰۰ آمپر سه پل کشویی سری NW قدرت قطع ۱۰۰kA

NW10H23P2AF

میکرولوجیک ۲

Main
range of product
Masterpact NW
product or component type
Basic frame
device short name
Masterpact NW10
circuit breaker name
Masterpact NW10H2
poles description
۳P
network type
AC
breaking capacity code
H2
suitability for isolation
Yes conforming to IEC 60947-2
utilisation category
Category B
Complementary
network frequency
۵۰/۶۰ Hz
control type
Push-button
mounting mode
Fixed
[In] rated current
۱۰۰۰ A at 40 °C
[Ui] rated insulation voltage
۱۰۰۰ V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
۱۲ kV conforming to IEC 60947-2
[Icm] rated short-circuit making capacity
۱۸۷ kA 525 V AC at 50/60 Hz
۱۸۷ kA 690 V AC at 50/60 Hz
[Ue] rated operational voltage
۶۹۰ V AC 50/60 Hz conforming to IEC 60947-2
circuit breaker CT rating
۱۰۰۰ A
breaking capacity
۸۵ kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
۸۵ kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
۱۰۰ kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
۱۰۰ kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
۱۰۰ kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity
۸۵ kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
۸۵ kA at 690 V AC 50/60 Hz conforming to IEC 60947-2
protection type
Without protection
mechanical durability
۱۲۵۰۰ cycles without maintenance conforming to IEC 60947-2
۲۵۰۰۰ cycles with maintenance conforming to IEC 60947-2
electrical durability
۱۰۰۰۰ cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
۱۰۰۰۰ cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 10000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-23A: 10000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
AC-3: 6000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
connection pitch
۱۱۵ mm
[Icw] rated short-time withstand current
۵۰ kA 3 s conforming to IEC 60947-2
۸۵ kA 1 s conforming to IEC 60947-2
integral instant protection
۱۷۱…۲۰۹ kA
maximum breaking time
۲۵ ms
maximum closing response time
۷۰ ms
height
۳۵۲ mm
width
۴۲۲ mm
depth
۲۹۷ mm
Environment
standards
IEC 60947-2
product certifications
ASTA
ASEFA
pollution degree
۴ conforming to IEC 60664-1
ambient air temperature for operation
-۲۵…۷۰ °C
ambient air temperature for storage
-۴۰…۸۵ °C